Three Phase Power

...

Three Phase Power

Three Phase Power Definition

It is found that generation of three phase power is more economical than generation of single phase power. In three phase electric power system the three voltage and current waveform are 120o offset in time in each cycle of power. That means each voltage waveform has phase difference of 120o to other voltage waveforms and each electric current waveform has phase difference of 120o to other electric current waveforms. Three phase power definition states that in an electrical system, three individual single phase powers are carried out by three separate power circuits. The voltages of these three powers are ideally 120o apart from each other in time - phase. Similarly, the currents of these three powers are also ideally 120o apart from each other. Ideal three phase power system implies balanced system.

A three phase system is said to be unbalanced when either at least one of the three phase voltages is not equal to other or the phase angle between these phases is not exactly equal to 120o.

Advantages of three phase system

There are many reason due which three phase power is more preferable than single phase power. 

1) The single phase power equation is
P = Vm.Imsinωt.sin(ωt − φ)
which is time dependent function. Whereas three phase power equation is
P = 3.(Vm/√2).(Im/√2).cosφ 
which is time independent constant function. Hence the single phase power is pulsating. This generally does not effect the low rating motor but in larger rated motor it produces excessive vibration. So three phase power is more preferable for high tension power load. 

2) The rating of a three phase machine 1.5 times grater than that of same size single phase machine.

3) Single phase induction motor has no starting torque so we have to provide some auxiliary means of starting, but three phase induction motor is self starting - does not require any auxiliary means.

4) Power factor and efficiency both are greater in case of three phase system.

Three Phase Power Equation

For determination the expression of three phase power equation i.e. for three phase power calculation we have to first consider an ideal situation where the three phase system is balanced. That means voltages and currents in each phase differ from their adjacent phase by 120o as well as the amplitude of each electric current wave is same and similarly amplitude of each voltage wave is same. Now, lets the angular difference between voltage and current in each phase of three phase power system is φ.

Then the voltage and current of red phase will be
VR = Vmsinωt and IR = Imsin(ωt − φ) respectively

the voltage and current of yellow phase will be
VY = Vmsin(ωt − 120o) and IY = Imsin(ωt − φ − 120o) respectively

and the voltage and current of blue phase will be
VB = Vmsin(ωt + 120o) and IB = Imsin(ωt − φ + 120o) respectively

Therefore, the expression instantaneous power in red phase is 
VR. IR = Vm. Imsinωt.sin(ωt − φ)

Similarly the expression instantaneous power in yellow phase is 
VY. IY = Vm.Imsin(ωt. − 120o)sin(ωt − φ − 120o)

Similarly the expression instantaneous power in blue phase is 
VB. IB = Vm.Imsin(ωt + 120o)sin(ωt − φ + 120o)

The total three phase power of the system is summation of the individual power in each phase

P = VR.IR + VY. IY + VB. IB

   = Vm.Imsinωt.sin(ωt − φ) 
+ Vm.Imsin(ωt − 120o)sin(ωt − φ − 120o) 
+ Vm.Imsin(ωt + 120o)sin(ωt − φ + 120o)

   = Vm.Im[sinωt.sin(ωt − φ) + sin(ωt − 120o)sin(ωt − φ − 120o) + sin(ωt + 120o)sin(ωt − φ + 120o)]

   = Vm.Im.(1/2)[2.sinωt.sin(ωt − φ) 
+ 2.sin(ωt − 120o)sin(ωt − φ − 120o) 
+ 2.sin(ωt + 120o)sin(ωt − φ + 120o)]

   = Vm.Im.(1/2)[cos(ωt − ωt + φ) − cos(ωt + ωt − φ)
   + cos(ωt. − 120o − ωt. + 120o + φ) − cos(ωt − 120o + ωt − 120o − φ)
   + cos(ωt + 120o − ωt − 120ot + φ) − cos(ωt + 120o + ωt + 120o − φ)]

    = Vm.Im.(1/2)[cosφ − cos(2.ωt − φ) + cosφ − cos(2.ωt − 240o − φ) + cosφ − cos(2.ωt + 240o − φ)]

    = Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) − cos(2.ωt − 240o − φ) − cos(2.ωt + 240o − φ)]

    = Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) − 2.cos(2.ωt − φ).cos(240o)]

    = Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) − 2.cos(2.ωt − φ).{−1/2}]

    = Vm.Im.(1/2)[3.cosφ − cos(2.ωt − φ) + cos(2.ωt − φ)]

    = 3.(Vm/√2).(Im/√2).cosφ 

    = 3VIcosφ This is three phase power equation

The above expression of power shows that the total instantaneous three phase power is constant and equal to three times of the real power per phase. In case of single phase power expression we fund that there are both reactive power and active power components, but in case of three phase power expression the instantaneous power is constant. Actually in three phase system, the reactive power in each individual phase is not zero but sum of them at any instant is zero.


--

2:41 AM

Single Phase Power

...

Single Phase Power

A single phase transmission system is practically not available but still we should know first the basic concept of single phase power before going through modern 3 phase power system.

Before going to details about single phase power, let's try to understand different Parameters of Electrical Power System

Three basic parameters of Electrical Power System are resistance, inductance and capacitance.

Resistance

The resistance of power circuit or simply resistor, consumes ohmic energy. While electric current flows through a resistor there will not be any phase difference between the voltage and current, that means electric current and voltage are in same phase the phase angle between them is zero. If I current flows through a resistance R for t seconds then total energy consumed by the resistor is I2.R.t. This power is known as active power

Inductance

Inductance of the system or simply inductor stores magnetic field energy during positive half cycle and gives away during negative half cycle of single phase power supply. If a current 'I' flows through a coil of inductance L Henri, the energy stored in the coil in form of magnetic field is given by

1L.I2
2

The power associated with an inductance is reactive power.

Capacitance

Capacitance of the system or simply capacitor, stores electric field energy during positive half cycle and give away during negative half cycle of supply. The energy stored between two parallel metallic plates of potential difference V and capacitance across them C, is expressed as

1C.V2
2

This energy is stored in form of electric field. The power associated with an capacitance is also reactive power.

Active Power and Reactive Power

Let us consider an single phase power circuit in which current lags behind the voltage by an angle φ. 
Let the instantaneous voltage v = Vm.sinωt 
then the instantaneous current can be expressed as i = Im. sin(ωt - φ).
Where,Vm and Im are the maximum values of sinusoidal system voltage and current respectively
The instantaneous power is given by

p = v.i = Vm.sinωt. Im. sin(ωt - φ)

           =1Vm. Im.2.sinωt. sin(ωt - φ)
2
           = 1Vm. Im.[{cosωt. cos(ωt - φ) + sinωt. sin(ωt - φ)} – { cosωt. cos(ωt - φ) - sinωt. sin(ωt - φ)}]
2
           =1Vm. Im.[cos{ωt - (ωt - φ)} - cos{ωt + (ωt - φ)}]
2
           = 1Vm. Im.[cos φ - cos(2ωt - φ)]
2

Active Power

Resistive Power

Let's take the condition first where the single phase power circuit is fully resistive, that means the phase angle between voltage and current φ = 0; and hence

p = 1Vm. Im.[1 - cos2ωt]
2
active power

From the above equation it is clear that whatever may be the value of ωt the value of cos2ωt can not be greater than 1 hence the value of p can not be negative. The value of p is always positive irrespective of the instantaneous direction of voltage v and current i, that means the energy is flowing in its conventional direction e.i. from source to load and p is the rate of energy consumption by the load and this is called active power. As this power is consumed due to resistive effect of an electrical circuit hence sometimes it is also calledresisteive power



Reactive Power

Inductive Power

Now consider a situation when the single phase power circuit is fully inductive, that means the current lags behind the voltage by an angle φ = + 90o. Putting φ = + 90o

in the equation p = 1Vm. Im.[cos φ - cos(2ωt - φ)] we get,
2
p =1Vm. Im.[0 - cos(2ωt - 90o)]
2
   = − 1Vm. Im.sin2ωt
2
inductive power

In the above expression, it is found that the power is flowing in alternative directions. From 0o to 90o it will have negative half cycle, from 90o to 180o it will have positive half cycle, from 180oto 270o it will have again negative half cycle and from 270o to 360o it will have again positive half cycle. Therefore this power is alternating in nature with a frequency, double of supply frequency. As the power is flowing in alternating direction e.i. from source to load in one half cycle and from load to source in next half cycle the average value of this power is zero. Therefore this power does not do any useful work. This power is known as reactive power. As the above explained reactive power expression is related to fully inductive circuit, this power is also called inductive power

This can be concluded as if the circuit is purely inductive, energy will be stores as magnetic field energy during positive half cycle and give away during negative half cycle and rate at which this energy changes, expressed as reactive power of inductor or simply inductive power and this power will have equal positive and negative cycle and the net value will be zero.

Capacitive Power

Let us now consider the single phase power circuit is fully capacitive, that is the current leads the voltage by 90o, therefore φ = - 90o.

Putting this value in the equation p = 1Vm. Im.[cos φ - cos(2ωt - φ)] we get,
2
p =1Vm. Im.[0 - cos{2ωt - ( - 90o)}]
2
   = 1Vm. Im.sin2ωt
2
capacitive power

Hence in the expression ofcapacitive power, it is also found that the power is flowing in alternative directions. From 0o to 90o it will have positive half cycle, from 90o to 180o it will have negative half cycle, from 180o to 270o it will have again positive half cycle and from 270o to 360o it will have again negative half cycle. So this power is also alternating in nature with a frequency, double of supply frequency. Therefore, as inductive power, the capacitive power does not do any useful work. This power is also a reactive power.



Active Power and Reactive Power

The power equation can be re-written as

p = Vm. Im.[cosφ – cos(2ωt - φ)]

    = Vm. Im.[cosφ – cosφ cos2ωt - sinφ sin2ωt]

    = Vm. Im.cosφ(1 – cos2ωt) – Vm. Imsinφsin2ωt

This above expression has two consonants; first one is Vm. Im.cosφ(1 – cos2ωt) which never goes negative as because value of (1 – cos2ωt) always greater or equal zero but can not have a negative value. active power and reactive powerThis portion of the single phase power equation represents the expression of reactive power which is alternatively known as real power or true power. The average of this power will obviously have some non zero value means the power physically does some useful work and that is why this power is also called real power or sometimes it is referred as true power. This portion of the power equation represents the reactive power which is alternatively known as real power or true power. 
Second term is Vm. Im.sinφsin2ωt which will have negative and positive cycles. Hence average of this component is zero. This component is known as reactive component as it travels back and forth on the line without doing any useful work.

Both active power and reactive power have same dimensions of watts but to emphasize the fact that reactive component represents a non-active power, it is measured in terms of volt-amperes reactive or in short VAR.


--

2:39 AM

Wheatstone Bridge and Wheatstone Bridge Theory

...

Wheatstone Bridge

For measuring accurately any resistance Wheatstone Bridge is widely used. There are two known resistors, one variable resistor and one unknown resistor connected in bridge form as shown below. By adjusting the variable resistor the current through the Galvanometer is made zero. When the current through the galvanometer becomes zero, the ratio of two known resistors is exactly equal to the ratio of adjusted value of variable resistance and the value of unknown resistance. In this way the value of unknown resistance can easily be measured by using a Wheatstone Bridge.

Wheatstone Bridge Theory

The general arrangement of Wheatstone bridge circuitis shown in the figure below. It is a four arms bridge circuit where arm AB, BC, CD and AD are consisting of resistances P, Q, S and R respectively. Among these resistances P and Q are known fixed resistances and these two arms are referred as ratio arms. An accurate and sensitive Galvanometer is connected between the terminals B and D through a switch S2. The voltage source of this Wheatstone bridge is connected to the terminals A and C via a switch S1 as shown. A variable resistor S is connected between point C and D. The potential at point D can be varied by adjusting the value of variable resistor. Suppose current I1 and current I2 are flowing through the paths ABC and ADC respectively. If we vary the resistance value of arm CD the value of current I2 will also be varied as the voltage across A and C is fixed. If we continue to adjust the variable resistance one situation may comes when voltage drop across the resistor S that is I2.S is becomes exactly equal to voltage drop across resistor Q that is I1.Q. Thus the potential at point B becomes equal to the potential at point D hence potential difference between these two points is zero hence current through galvanometer is nil. Then the deflection in the galvanometer is nil when the switch S2 is closed.

Now, from Wheatstone bridge circuit

current I1 =V
P + Q

and

current I2 = V
R + S

Now potential of point B in respect of point C is nothing but the voltage drop across the resistor Q and this is

I1.Q = V.Q-------------------(i)
P + Q

Again potential of point D in respect of point C is nothing but the voltage drop across the resistor S and this is

I2.S = V.S------------------(ii)
R + S
charles wheatstone

Equating, equations (i) and (ii) we get,

V.Q=V.S⇒ Q=S
P + Q R + SP + QR + S
⇒ P + Q=R + S⇒ P+ 1 =R+ 1⇒ P=R
Q SQSQS
⇒ R = SXP
Q

Here in the above equation, the value of S and P ⁄ Q are known, so value of R can easily be determined.

The resistances P and Q of the Wheatstone bridge are made of definite raio such as 1:1; 10:1 or 100:1 known as ratio arms and S the reostat arm is made continuously variable from 1 to 1,000 Ω or from 1 to 10,000 Ω

The above explanation is most basic Wheatstone Bridge theory.


--

2:36 AM

Sony Reports Higher Image Sensor Sales but Lowers Forecast

...
Slide 11 of Sony Q2 FY2012 earnings presentation says that "sales of ... image sensors are expected to be lower than previously anticipated, segment sales are expected to be lower than the August forecast". No reason for the forecast reduction is given.

Seeking Alpha earnings call transcript quotes Yoshinori Hashitani, Sony VP Investor Relations, saying that last quarter "sales of the image sensors increased because of strong demand of smartphones and other products".
2:35 AM

Basic Electrical Objective questions on transformers which you have to learn for exams.

...
-->



Write to me at marinenotes4u@gmail.com,283928@gmail.com.::MK::.
-->

Basic Electrical Objective questions which you have to learn for exams.

...
-->



Write to me at marinenotes4u@gmail.com,283928@gmail.com.::MK::.
-->

Miniature Circuit Breaker or MCB

...

Miniature Circuit Breaker or MCB

What is MCB ?

Nowadays we use more commonly Miniature Circuit Breaker or MCB in low voltage electrical network instead of fuse.

The MCB has some advantages compared to fuse.
1. It automatically switches off the electrical circuit during abnormal condition of the network means in over load condition as well as faulty condition. The fuse does not sense but Miniature Circuit Breaker does it in more reliable way. MCB is much more sensitive to over current than fuse.
2. Another advantage is, as the switch operating knob comes at its off position during tripping, the faulty zone of the electrical circuit can easily be identified. But in case of fuse, fuse wire should be checked by opening fuse grip or cutout from fuse base, for confirming the blow of fuse wire.
3. Quick restoration of supply can not be possible in case of fuse as because fuses have to be rewirable or replaced for restoring the supply. But in the case of MCB, quick restoration is possible by just switching on operation.
4. Handling MCB is more electrically safe than fuse.
Because of to many advantages of MCB over fuse units, in modern low voltage electrical network, Miniature Circuit Breaker is mostly used instead of backdated fuse unit.

Only one disadvantage of MCB over fuse is that this system is more costlier than fuse unit system.

miniature circuit breaker

Miniature Circuit Breaker Working Principle

There are two arrangement of operation of miniature circuit breaker. One due to thermal effect of over current and other due to electromagnetic effect of over current. The thermal operation of miniature circuit breaker is achieved with a bimetallic strip whenever continuous over current flows through MCB, the bimetallic strip is heated and deflects by bending. This deflection of bimetallic strip releases mechanical latch. As this mechanical latch is attached with operating mechanism, it causes to open the miniature circuit breaker contacts. But during short circuit condition, sudden rising of electric current, causes electromechanical displacement of plunger associated with tripping coil or solenoid of MCB. The plunger strikes the trip lever causing immediate release of latch mechanism consequently open the circuit breaker contacts. This was a simple explanation of miniature circuit breaker working principle.

Miniature Circuit Breaker Construction

Miniature circuit breaker construction is very simple, robust and maintenance free. Generally an MCB is not repaired or maintained, it just replaced by new one when required. A miniature circuit breaker has normally three main constructional parts. These are:

Frame of Miniature Circuit Breaker

The Frame of Miniature Circuit Breaker is a molded case. This is a rigid, strong, insulated housing in which the other components are mounted.

Operating Mechanism of Miniature Circuit Breaker

The Operating Mechanism of Miniature Circuit Breaker provides the means of manual opening and closing operation of miniature circuit breaker. It has three-positions "ON," "OFF," and "TRIPPED". The external switching latch can be in the "TRIPPED" position, if the MCB is tripped due to over-current. When manually switch off the MCB, the switching latch will be in "OFF" position. In close condition of MCB, the switch is positioned at "ON". By observing the positions of the switching latch one can determine the condition of MCB whether it is closed, tripped or manually switched off.

Trip Unit of Miniature Circuit Breaker

The Trip Unit is the main part, responsible for proper working of miniature circuit breaker. Two main types of trip mechanism are provided in MCB. A bimetal provides protection against over load current and an electromagnet provides protection against short-circuit current.

miniature circuit breaker working principle

There are three mechanisms provided in a single miniature circuit breaker to make it switched off. If we carefully observe the picture beside, we will find there are mainly one bi - metallic strip, one trip coil and one hand operated on - off lever. Electric current carrying path of a miniature circuit breaker shown in the picture is like follows. First left hand side power terminal - then bimetallic strip - then current coil or trip coil - then moving contact - then fixed contact and - lastly right had side power terminal. All are arranged in series. construction of miniature circuit breakerIf circuit is overloaded for long time, the bi - metallic strip becomes over heated and deformed. This deformation of bi metallic strip causes, displacement of latch point. The moving contact of the MCB is so arranged by means of spring pressure, with this latch point, that a little displacement of latch causes, release of spring and makes the moving contact to move for opening the MCB. The current coil or trip coil is placed such a manner, that during short circuit fault the mmf of that coil causes its plunger to hit the same latch point and make the latch to be displaced. Hence the MCB will open in same manner. Again when operating lever of the miniature circuit breaker is operated by hand, that means when we make the MCB at off position manually, the same latch point is displaced as a result moving contact separated from fixed contact in same manner. So, whatever may be the operating mechanism, that means, may be due to deformation of bi - metallic strip , due to increased mmf of trip coil or may due to manual operation, actually the same latch point is displaced and same deformed spring is released, which ultimately responsible for movement of the moving contact. When the the moving contact separated from fixed contact, there may be a high chance of arc. This arc then goes up through the arc runner and enters into arc splitters and is finally quenched. When we switch on an MCB, we actually reset the displaced operating latch to its previous on position and make the MCB ready for another switch off or trip operation.


--

2:08 AM

HRC Fuse or High Rupturing Capacity Fuse

...

HRC Fuse or High Rupturing Capacity Fuse

hrc fuse cartridge fuse

HRC fuse or High Rupturing Capacity Fuse. In that type of fuse, the fuse wire or element can carry short circuit heavy current for a known time period. During this time if the fault is removed, then it does not blow off otherwise it blows off or melts.
The enclosure of HRC fuse is either of glass or some other chemical compound. This enclosure is fully air tight to avoid the effect of atmosphere on the fuse materials. The ceramic enclosure having metal end cap at both heads, to which fusible silver wire is welded. The space within the enclosure, surrounding the fuse wire or fuse element is completely packed with a filling powder. This type of fuse is reliable and has inverse time characteristic, that means if the fault current is high then rupture time is less and if fault current is not so high then rupture time is long.

Operation of HRC fuse

When the over rated current flows through the fuse element of High Rupturing Capacity Fuse the element is melted and vapourized. The filling powder is of such a quantity that the chemical reaction between the silver vapour and the filling powder forms a high resistance substance which very much help in quenching the arc.


--

2:07 AM

What is electrical fuse ?

...

Electrical Fuse

What is electrical fuse ?

In normal working condition of electrical network, the electric current flows through the network is within the rated limit. If fault occurs in the network mainly phase to phase short circuit fault or phase to ground fault, the network current crosses the rated limits. This high electric current may have very high thermal effect which will cause a permanent damage to the valuable equipments connected in the electrical network. So this high fault current should be interrupted as fast as possible. This is what an electrical fuse does. A fuse is a part of the circuit which consists of conductor which melts easily and breaks the connection when electric current exceeds the predetermined value.

An electrical fuse is a weakest part of an electrical circuit which breaks when more than predetermined current flows through it.

Fuse wire

The function of fuse wire is to carry the normal current without excessive heating but more than normal current when pass through fuse wire, it rapidly heats up and melts.

Materials used for fuse wires

The materials used for fuse wires are mainly tin, lead, zic, silver, antimony, copper, aluminium etc.

Fuse wire rating

The melting point and specific resistance of different metals used for fuse wire

MetalMelting point Specific Resistance
Aluminium240oF 2.86 μ Ω - cm
Copper2000oF 1.72 μ Ω - cm
Lead624oF 21.0 μ Ω - cm
Silver1830oF 1.64 μ Ω - cm
Tin463oF 11.3 μ Ω - cm
Zinc787oF 6.1 μ Ω - cm

Some important terms need for fuse.

1. Fuse it is already defined earlier.

2. Fuse wire, it is also defined earlier

3. Minimum fusing current: It is minimum value of current due to which fuse melts.

4. Current rating of fuse: It is maximum value of current due to which fuse does not get melt.

5. Fusing factor: This is the ratio of minimum fusing current and current rating of fuse.
Therefore, fusing factor = Minimum fusing current / current rating of fuse.
The value of fusing factor is always more than 1.

6. Prospective Current in fuse: Before melting, the fuse element has to carry the short circuit current through it.The prospective current is defined as the value of current which would flow through the fuse immediately after a short circuit occurs in the network.

7. Melting time of fuse or pre arcing time of fuse: This is the time taken by an fuse wire to be broken by melting. It is counted from the instant, the over current starts to flow through fuse, to the instant when fuse wire is just broken by melting.

8. Arcing time of fuse: After breaking of fuse wire there will be an arcing between both melted tips of the wire which will be extinguished at the current zero. The time accounted from the instant of arc initiated to the instant of arc being extinguished is known as arcing time of fuse. 

9. Operating time of fuse: When ever over rated current starts to flow through a fuse wire, it takes a time to be melted and disconnected, and just after that the arcing stars between the melted tips of the fuse wire, which is finally extinguished. The operating time of fuse is the time gap between the instant when the over rated current just starts to flow through the fuse and the instant when the arc in fuse finally extinguished. That means operating time of fuse = melting time + arcing time of fuse.

Current Carrying Capacity of fuse wire

Current carrying capacity of a fuse wire depends upon numbers of factors like, what material used for it, what are the dimension of it, i.e. diameter and length, size and shape of terminals used to connect it, and the surrounding.

Fuse Law

Fuse law determines the cuyrrent carrying capacity of a fuse wire. The law can be established in the following way. At steady state condition that is when fuse carry normal current without increasing its temperature to the melting limit. That means at this steady state condition, heat generated due to current through fuse wire is equal to heat dissipated from it.

Heat generated = I2.R 
Where R is the resistance of the fuse wire

I2.ρ. l
a

Where ρ is the resistivity, l is the length and a is the cross sectional area of fuse wire

I2.ρ. l
πd2/4

Where d is the diameter of fuse wire

I2.K1.l.............(i)
d2

Where K1 is a constant

Heat lost ∝ surface area of fuse wire ∝ πd.l
Therefore, heat lost = K2.d.l .............(ii)
Where K2 is a constant

Now, equating (i) & (ii), we get,

I2.K1.l= K2.d.l
d2

⇒ I2 = K.d3

Where K =K2is another costant
K1

⇒ I = K.d3/2
⇒ I = K.d1.5

This is known as fuse law

Metalvalue of K when d is measured in mm
Aluminium59
Copper80
Iron24.6
Lead 10.8

Rewirable or Kit kat fuse unit

rewirable or kit kat fuse unit

This is most commonly used fuse in our day to day life. This fuse has mainly two parts. The unit in which the incoming and outgoing line or phase wire connected permanently is known as fuse base. The removable parts which hold a the fuse wire and fits into the base, is known as fuse carrier. The fuse carrier is also known as cutout.

cartridge fuse

In cartridge fuse the fuse wire is enclosed in a transparent glass tube or bulb, the whole unit is sealed off. In case the fuse blows, it is to be replaced by new one as the cartridge fuse can not be rewired due to its sealing.


Lead – tin Alloy Fuse Wire or Eutectic Alloy Fuse Wire

For small value of current interruption lead – tin alloy fuse wire has been used in past. The most preferred lead – tin alloy for fuse wire containing 37% lead and 63% tin. This alloy fuse wire is also known as known as Eutectic Alloy Fuse Wire. This type of alloy has some specific characteristics due to which this is preferred as fuse wire.

1. It has the high brinnel hardness and has less tendency to spread over.
2. The alloy metal is quite homogeneous.
3. If the fusing characteristics of eutectic alloy and other composition of alloys is studied there is only one arrest point in eutectic alloy as compared to two other types of alloys.

Approximate fusing currents of lead – tin alloy fuse wire in air

Diameter of 
wire in inch
Fusing Current
in A
Maximum safe 
Current in A
0.023 2
0.0223.52.3
0.02442.6
0.02853.3
0.032 64.1
0.0367 4.8
0.048107
0.0641611

NB : - The minimum length of the fuse wire used must be 2.5 to 3.5 inches. The values in the above table are true only when the fuse wire does not touches the fuse grip body because when the fuse wire comes in contact with porcelain or other the value of fusing current increases as the heat dissipation rate from the current carrying fuse wire, is increased. Hence precaution should always be taken during rewiring a fuse wire on a fuse grip so that it should not touch the fuse grip body.


--

2:06 AM

Marine Electrical Fuses

...
Fuses
High current flow through a thin fuse wire will raise its temperature causing it to melt and break the circuit before the current excess reaches a level sufficient to damage other, more substantial, parts of the system. Melting temperature depends on the material used (tinned copper in rewireable fuses melts at 1080ºC, the silver in cartridge fuses at 960ºC). The wire is sized so that the normal current is carried without overheating, but due to the resistance of the relatively small wire, that excess current will produce heat sufficient to melt it. Current rating gives the normal current that may be carried: minimum fusing current is the smallest current that will cause melting.

A fuse will melt much quicker with very large fault current than when the value of fault current is only just above the minimum fusing current. Time/current characteristics are found by testing six or more of the same type of fuse at different currents and plot ting the results. The bottom current for the test is not more than 1.05 X minimum fusing current, and the top current is one that will melt the wire in not more than 0.5 second. The other test currents are equally spaced between these. Fuses are rated for particular ac. and/or d.c. voltages
cartridge fuse
Cartridge Fuses
High Rupture Capacity (HRC) fuses have silver wire enclosed in a quartz powder filled ceramic tube with metal end caps . Arcing when this type of fuse blows is buried in the powder, fusion of which in the arc path helps to extinguish it.
HRC fuses can be used for very high fault levels: deterioration is negligible; they have accurate time/current characteristics and reliability for discrimination; they are safer if accidentally inserted on a fault: there is no issue of smoke or flame; cartridges are sized to ensure that the correct value fuse is fitted.

Semi-enclosed Fuses
The rewireable fuse has an insulated carrier for safe handling and containment of the wire in an asbestos lined tube 
The wire is easily replaced after operation, but the des is open to abuse as too heavy a wire can be used which could mask a fault and also cause severe arcing if it did operate. Another fault is that of premature failure if the wire is made thinner by oxidation or con tact with air, or by being stretched when fitted (a problem with wire made of lead, tin or an alloy of the two).

Fuses in Service
Fuses may be used as the only protection in a steady load circuit, such as for lighting. An ac. motor with its high starting current and varying load has fuses in each of the supply conductors, but fitted as a backup for the other forms of protection and to break the circuit in the event of a short-circuit current greater than that which the ordinary contact breakers are designed to interrupt without damage. Very accurate time/current characteristics are needed for fuses used in conjunction with other safety devices, to ensure that the overload trip is allowed time to operate for moderate over- current but that the fuse blows first if there is very high short-circuit current.

--

2:04 AM

Explain the operation of a main engine Exhaust valve which is operated hydraulically?

...
Explain the operation of a main engine Exhaust valve which is operated hydraulically?

A: A hydraulic pump, operated by the exhaust cam supplies the hydraulic oil to operate the valve. A small permanent vent ensures that air is excluded fro the system. This leak off of oil returned to the air spring cylinder for lubrication and is then drained away. The hydraulic pump is supplied with a make up supply via a non return valve and a relief valve.
As the cam rotates in time with the crankshaft it lifts the plunger on the hydraulic pump. Oil displaced by the pump plunger displaces the exhaust valve operating piston, moving it and the exhaust valve spindle downwards against the air spring pressure and opening the exhaust valve.
The exhaust gas passes over the spinner, rotating the exhaust valve spindle, this reduces distortion due to uneven temperatures and helps remove deposits as the valve closes .when the cam passes its peak, the pump plunger moves downwards and the compressed air in the air spring closes the valve. As the operating piston enters the damping pin, the closing is slowed, thus preventing hammering of the valve.

--

1:51 AM

High Speed Imaging Circa 1980

...
This Youtube video teardown shows internal design of Kodak Spin Physics high-speed digital camera, originally released in 1980. The camera had a resolution of 240x192 and frame rate of 2000fps - quite impressive numbers for a 30+ year old technology based on 34um pixels:



Here is the sensor's corner snapshot from the video:

2:21 PM

Altasens Talks about Stacked Sensor Advantages

...
Altasens' patent application US20120267511 "Image sensor with hybrid heterostructure" by Lester Kozlowski has few interesting claims:

First, a stacked sensor structure is proposed:


The pixel array uses "optimized" pmos transistors. An example pixel capable of GS, S&H and CDS is shown on Fig. 6:


The main advantages of the stacked structure are (1) very good global shutter efficiency and (2) lower noise due to a special pmos transistor "optimization":

"FIGS. 7 and 8 [not shown here] compare the read noise achievable with optimized PMOS technology vs. standard CMOS technology wherein the source follower is formed in NMOS having flicker noise lower than readily achieved in common foundry processes, i.e., very good compared to what is readily available. Even so, the PMOS global shutter can yield a read noise of 1 e− (or holes) at a sense capacitance of 5 fF. The NMOS global shutter circuit instead has read noise of 3.5 e− at 5.5 fF. More importantly for long term development, the PMOS solution goes well below 1 e−0 as the sense capacitance is reduced while the NMOS solution plateaus well above 2 e−."
9:50 AM

Toshiba Announces 8MP 1/3.2-inch BSI Sensor

...
Toshiba published a product page of 8MP 1.4um BSI pixel-based T4K34 sensor. The sensor did not appear on the previously published Toshiba roadmap. The new sensor is quite fast, delivering 30fps at full resolution and the same frame rate in 1080p mode. Its ADC resolution is selectable between 8b or 10b.

2:28 AM

Digital Camera Sensors Database

...
The new Digital Camera Database has an information on pixel size, sensor areas and more from 3281 digital cameras. The information is nicely presented in graphical and numerical form. It's hard to believe that the whole web site is just one-man job!

Thanks to GB for the link!
12:21 PM

Kasalis Announces Pixid 300 Pro Availability

...
Kasalis announces the release of its Pixid 300 line of fully automated camera module assembly and test systems, featuring its active alignment technology. The Pixid 300 Pro and Pixid 300 Test models are now available for shipment.

"The increasing demands for improved image quality in mobile cameras has transformed the camera module industry, which now needs a cost-effective solution to meet the higher level of precision required in the alignment process," said Justin Roe, president of Kasalis. "The Pixid 300 Pro is a clear breakthrough that is changing the cost-benefit equation of active alignment for the whole industry. We have created a disruptive technology – the Pixid 300 Pro performs pre-dispense tests, adhesive dispense, dispense verification, active alignment, UV cure, and post-alignment tests all within 15 seconds, with a throughput of over 240 units per hour, and all for very competitive pricing."

The Pixid 300 Pro model is a fully automated manufacturing system featuring active alignment, customizable optical testing options, Adaptive Intelligence SPC, and automated adhesive dispense and UV cure. Each stage of assembly is performed in parallel to obtain the fastest possible throughput time. Adaptive Intelligence is a software suite that is embedded in the Pixid systems and improves the alignment process by using the machine feedback to improve its algorithms, thereby attaining faster speeds and improved yields. In addition to the Pixid 300 Pro, the series includes the Pixid 300 Test model, which is intended purely for the automated functional testing of camera modules.

The Pixid 300 series systems are designed for high volume production of camera modules such as those used in smartphones, automotive applications, webcams, medical imaging, and security cameras. Kasalis has designed all of the Pixid systems to solve industry challenges, provide easy upgrading and maintenance through modular parts, and to align a camera lens to a sensor in up to six degrees of freedom to obtain the best possible focus quality across the entire image sensor. As technology in mobile electronics advances, camera modules assembled with precision alignment are increasingly important.

Pixid 300 Pro
12:08 PM

Workshop on Radiation Effects in Optoelectronic Detectors

...
2nd Workshop on Radiation Effects in Optoelectronic Detectors is to be held on November 28-29, 2012 in Toulouse, France, co-organised by CNES, ASTRIUM, THALES ALENIA SPACE, SODERN, ISAE. The program has papers devoted to radiation damage in CCD and CMOS senosrs:

Investigations on performance of Electron Multiplied CCD detectors (EMCCDs) after radiation for observation of low light star-like objects in scientific space missions
H. Michaelis, T. Behnke, S. Mottola, A. Krimlowski, German Aerospace Center, DLR, Institute of Planetary Research, Berlin (Germany), A. Holland, XCAM Ltd, Northampton, (UK), M. Schmid, Ingenieurbüro Schmid, Berlin (Germany)

The GAIA Radiation test campaigns: an historical review
D. Marchais, ASTRIUM SAS

A Comparison of Radiation Damage in CCDs From a Number of Flight Programmes
P. Jerram, E2V technologies

In-Orbit Results from CNES Satellite CCDs
A. Bardoux, A. Penquer, O. Gilard, R. Ecoffet, CNES, M. Auvergne, LESIA

Response of 3T and 4T Multi-Variant CMOS Image Sensors to Proton Radiation
A. Pike, J. Pratlong E2V Technologies

New Radiation Test Results on HAS2 CMOS Image Sensor
D. Hervé, M. Beaumel, SODERN, D. Van Aken, ON Semiconductor

Dark current degradation of a 5T 0.18µm e2v CMOS image sensor under gamma and proton irradiation
T. Nuns, J.P. David, ONERA, E. Martin, O. Gilard, CNES

CMOS monolithic sensors for vertex detector applications: TID effects and bulk damage study
L. Ratti, S. Zucca, Università di Pavia and INFN Pavia, L. Gaioni, INFN Pavia, G. Traversi, Università di Bergamo and INFN Pavia, S. Bettarini, G. Rizzo, Università di Pisa and INFN Pisa, F. Morsani, INFN Pisa, L. Bosisio, I. Rashevskaya, Università di Trieste and INFN Trieste

Radiation Effects in CMOS Image Sensor Isolation Oxides: Differences and Similarities with Thermal Oxides
M. Gaillardin, C. Marcandella, M. Martinez, P. Paillet, S. Girard, CEA DAM DIF, V. Goiffon, P. Magnan, M. Estribeau, ISAE, Image Sensor Research Team

Radiation Effects on Pinned Photodiode CMOS Image Sensors: Overview of Pixel Performance Degradation Due to Total Ionizing Dose
V. Goiffon, M. Estribeau, O. Marcelot, P.Cervantes, P. Magnan, P. Martin-Gonthier, R. Molina, F. Corbière, ISAE, Image Sensor Research Team, M. Gaillardin, S. Girard, P. Paillet,C. Marcandella, CEA DAM DIF, C. Virmontois, (Formerly at ISAE, now at CNES)

Recent radiation testing on 180 nm and 110 nm CMOS Image Sensor processes
J. Bogaerts, K. Van Wichelen, E. Gillisjans, G. Lepage, G. Meynants, CMOSIS nv

Displacement Damage Effects on Pinned Photodiode CIS
C. Virmontois, A. Bardoux, CNES, V. Goiffon, P. Magnan, F. Corbière, ISAE, Image Sensor Research Team, S. Girard, CEA DAM DIF

Single Event Effects in CMOS Image Sensors
V. Lalucaa, V. Goiffon, P. Magnan, ISAE, Image Sensor Research Team, G. Rolland, S. Petit, CNES

Vulnerability of CMOS image sensors in megajoule class laser harsh environment
P. Paillet, S. Girard, O. Duhamel, J.-L. Bourgade, S. Darbon, A. Rousseau, CEA, DAM, DIF, V. Goiffon, A. Chabane, P. Magnan, P. Cervantes, P. Martin-Gonthier, M. Estribeau, ISAE, Image Sensor Research Team, J. Baggio, CEA CESTA, V. Yu. Glebov, G. Pien, and T. C. Sangster, LLE, University of Rochester

Development of radiation tolerant EUV detectors and hybrid imagers
P. de Moor, IMEC

Specific tools developed for radiation tests at cryogenic temperature
A. Le Paih, F. Perrier, SOFRADIR

Radiation results on cooled infrared detectors
F. Perrier, A. Le Paih, SOFRADIR

Radiation testing of the MSI and Proba-V linear arrays
J. Vermeiren, Xenics

Evaluation of InGaAs array detector suitability to space environment
L. Tauziède, K. Beulé, M. Boutillier, F. Bernard, CNES, J. L. Reverchon, Alcatel-Thales-III-V Lab, A. Buffaz, Pléiades technologies

Prototype ASIC development for space large format NIR/SWIR detector array
P. Gao, B. Dupont, B. Dierickx, Caeleste, G. Verbruggen, S. Gielis, EASICS

Roscosmos Test Facilities For Optoelectronic Devices Space Radiation Hardness Control
V. Anashin, G. Protopopov, P. Chubunov, A. Kozyukov, Institute Of Space Device Engineering

The Development of Displacement Damage Test Guidelines for Imaging Devices
M. Robbins, Surrey Satellite Technology Limited

The workshop also has few tutorials:

Space Radiation Environment
Robert Ecoffet, CNES

Degradation mechanisms and impact on performances: Total ionizing dose effects
Jean-Pierre David, Thierry Nuns, ONERA

Degradation mechanisms and impact on performances: Displacement damage effects
Christophe Inguimbert, ONERA

Registration is free of charge, but requires mandatory on-line registration (before November 23rd): http://cnes.cborg.net/cct/bipublicgb.html

Thanks to AT for sending me the program!
11:38 AM

Easy Ways On How To Test A Fuse With A Multimeter

...

Easy Ways On How To Test A Fuse With A Multimeter

fuse

Typical example of fuses

 

It's very easy on how to test a fuse. Fuse is a very thin wire, which either melts or vaporizes when current flow through it exceeded the fuse rating. The thin wire of fuse may be made of aluminum, tin-coated copper or nickel. The resulting open in the circuit stops current to flow. In electronic equipment, most fuses are cylindrical glass or ceramic type with a metal cap at each end! The current rating and voltage also can be seen in one of the two metal end caps.

 

There are two popular physical sizes: 1 – ¼ X ¼ - inch and 5X20mm. The 1 – ¼ X ¼ - inch size is used in many automobiles. You'll find both sizes in many electronic equipment, but the smaller 5 X 20mm has become more common. Fuses are available with current ratings from 1/500 Ampere to hundreds of amperes.

 

Before showing you on how to test or check a fuse, first you need to understand the purpose of a fuse. The function of fuses is to stop higher than normal current to flow to an electronic circuit-it is designed to protect equipment and save electronic components from being damaged and also stop overheating, which could cause a fire. Sometimes though there were lightning strike on an equipment, you will be surprised that only fuse were damaged and not the power supply section or components. 

 

slow blow fuseThere are two basic types of fuses which is the fast acting and slow blow type. The fast acting fuse will open very quickly when their particular current rating is exceeded. This is very important for analogue multimeter, which can quickly be destroyed when too much current flows through them, for even a very small amount of time.

Even if you are an experienced repairer, sometimes we do made mistake by accidentally touching the probe to the testing points where it should not be touch! The slow blow fuse has a coiled construction inside the glass. Slow blow fuses are designed to open only on a continued overload, such as a short circuit. The function of the coiled construction is to stop the fuse from blowing on just a temporary current surge.

 

Don't replace a slow blow fuse in place of a fast acting fuse because it may not open fast enough to prevent components damage under a high current condition. It's not dangerous to substitute a slow blow fuse with a fast-acting fuse, but it will probably open up unnecessarily every now and then when the equipment is first switch on such as when you switch on a Computer Monitor.

 testing fuses

A blown fuse can indicate how severe the short circuit is.

 

There's a secret for you, a blown fuse can indicate something about the problem. If the glass case of the fuse appears clear or transparent, and if you can still see the slight broken pieces of the fuse element, this means that there's no major short circuit in the circuit. Replacing the fuse with one of the same type and rating usually will bring the equipment back to life again. However, sometimes a replacement might blow the fuse right away when you switch on the equipment. To save the fuse, you can use the series light bulb trick which I'm going to share to you in other article.

 

Some fuses even die of old age because fuses have lifespan too. But if the inside of the glass fuse is black color or darkened, and there is no trace of the fuse element (the center connector), you know that there was a major short circuit somewhere in the circuit and most probably is the power supply unit.

 

how to test a fuse

 

Measuring a fuse on board with an analog multimeter

 

The common type and current rating of a fuse in a Monitor and Power Supply are slow blow 3.15A to 5 Ampere. Here is the part on how to test a fuse. Switch off the power of the equipment, remove the casing and you will see a fuse usually located in the Ac input area or power supply section. Measure the fuse with a either an analog or a digital multimeter. If you use an analog meter then select the lowest ohms range which is the x1 ohms.

 

 

 

Touch the probes to both end of the fuse. You can check the fuse while it still in circuit. A good fuse reading should showed continuity or read ZERO ohm. A blown fuse is open which will not show any reading on your meter. Testing fuse is one of the simplest tasks in electronic troubleshooting-it's easy and fast. For fuse replacement, use only the same current and voltage ratings as the original one.


--

10:30 AM

Testing procedure for fuses

...
Testing procedure for fuses
It is extremely important to understand that if a fuse looks good, it might not in fact be good! Fuses can appear to be fine and have a break in them so small that it cannot be seen by the naked eye! Therefore it is important to check a fuse with an Ohmmeter or a continuity tester instead of assuming that it is good. A significant percentage of all boards returned to Dinosaur as "dead" have nothing wrong with them other than a blown fuse. Assumptions can waste a lot of time! The fuse shown below looks perfectly good, but is open under one of the end caps!



Use a multimeter and set the range switch to the lowest resistance range to check the fuse. A good fuse will read 0 ohms (depending on what the meter reads when the leads are held together) and a bad fuse will read the same as holding the leads in the air. The illustrations below show how to test fuses, showing each fuse as good. There is no gray area, the fuse is either good or it is not.

Testing a standard fuse



Testing an automotive style fuse



You can also use a "battery operated continuity tester" as shown in the illustration below (also indicating a good fuse)*Important note: A standard test light without the built-in battery will not work! It must have a battery built-in to make the lamp light up!



--

10:25 AM