Showing posts with label actuator. Show all posts
Showing posts with label actuator. Show all posts

Industrial Valve Assemblies Using ROTEX Actuators

...
ROTEX Controls manufactures high quality pneumatic valve actuators, limit switches and solenoid valves used on industrial valves and dampers.

This video demonstrates some of the ways ROTEX actuators are mounted and assembled to valves along with limit switches and solenoids.



For more information, contact:
ROTEX USA
(888) 813 - 9772
www.rotexcontrolsusa.com

Valve Selection - Gate Valves

...
Fluid flow control in industrial processes is most often accomplished through the use of valves installed at specific locations in the piping system to start, stop, throttle, or divert the fluid flow. The application characteristics are broad and varied, resulting in an almost unmanageable menu of possible valve choices. Since we have limited time to spend on any task, it’s useful to employ a simple filter in your valve selection procedure. This generally allows for the elimination of a large group of candidates and allows your efforts to be quickly focused on potentially useful products. One filtering criteria that can be applied to industrial control valves is the valve type.

Valve type generally refers to the means employed to control fluid flow. The closure means and the valve characteristics associated with it can be used to determine whether a valve type may be suitable for your process application. Some common valve types include ball, gate, plug, and butterfly, with numerous variations and customization occurring within each type. Let’s consider the gate valve.

industrial gate valve with hand wheel actuator
Gate Valve With Handwheel
Courtesy WEY Valve
Gate valves have a movable wedge, often rectangular or round, that is positioned in the fluid flow path. This wedge, the “gate” or “disc”, is connected to a stem which extends to the exterior of the valve body. Motion of the stem will position the gate within the valve body to provide some degree of obstruction to the fluid flow path. Fully inserting the gate into the media path will shut off the flow, while successively withdrawing the gate will increase the opening through which fluid can pass and allows for increasing flow rates. Seals are provided along the planar surfaces where the gate contacts the valve body.

What are potential positive attributes of gate valves?

  • When fully open, these valves provide little or no restriction to fluid flow. In addition to having a fluid path cross section generally similar to the connected piping, the valve construction does not impose any change in the fluid flow direction as media passes through the valve. This valve type provides a straight through passage.
  • Gate valves can be employed bi-directionally, with flow control effectively available in both directions.
  • Installation space dimensions along the flow path are generally low, when compared to some other valve types.
  • The energy requirements to change valve position are generally low, since the gate movement is perpendicular to the flow direction.
  • The rate of closure is comparatively slow, inhibiting physical shock (hammering) in the connected piping system.

Here are some other attributes of gate valves.
gate valve with actuator
Gate Valve With Actuator
Courtesy DeZurik

  • As the valve opens, the seals are exposed to the fluid flow. The effects of media velocity and chemical aggressiveness on the seal material may cause deterioration at an unacceptable pace, especially in throttling applications.
  • Gate valve stems generally extend substantially from the valve body, as they must accommodate the mounting of any required actuator and the entire range of motion of the gate. Some installations may not be able to provide the needed space for this arrangement.
  • The slow opening and closing activity of gate valves may not be suitable for some applications.
  • Gate valves are not exceptional at throttling flow. Additionally, attempts at throttling flow may result in gate vibration. There is also concern about premature seal wear due to exposure to higher media velocities while throttling.

Your selection focus may be shifted by these general criteria. Combine your knowledge and understanding of your process and media with the experience and knowledge of valve and control experts to specify a valve configuration that will provide the performance you need.



ROTEX Pneumatic Valve Actuator Introduction

...
Here is a movie/slideshow introducing the ROTEX family of pneumatic valve actuators. The movie includes the ECV "Infinity line of rack and pinion actuators, the DRS scotch yoke series and the DRC and DRV large scale rack and pinion series.

Unique design and high performance features are explained and pictures of automated valve packages are included.


Intro to ROTEX Solenoids, Valve Actuators and Limit Switches

...
Introduction of ROTEX Controls product line of solenoid valves, Infinity ECV line of rack and pinion actuators, DRS and DRV scotch yoke actuators, and HYV hydraulic actuators and limits switches.

ROTEX offers a range of Solenoid Valves and Air Operated Valves used for handling almost any fluid with various of temperature, pressure or vacuum for use in Control and Automation applications.

ROTEX limit switches are designed to last and meet your required service conditions. Both the weather proof and explosion proof switches feature an aluminum die cast enclosure that is powder coated for superior corrosion resistance resulting in a weather proof enclosure to IP67. Stainless steel enclosures are available, also confirming to IP67.

Assembly Animation of ROTEX Rack & Pinion Actuators

...
Here is a good animation detailing the primary components and construction of the ROTEX ECV pneumatic valve actuator:



ROTEX ECV actuators distinguish themselves from other rack and pinion manufacturers by offering the following advanced features:
  • Self energizing V-Seal piston rings
  • Double rack & pinion
  • High corrosion resistance
  • Pinion supported on polyacetal bearings
  • Maximum working pressure 125 psig, optional 150 psig
  • No lubrication required
  • Temperature range -20 °F to +230 °F
  • Anodized body inside and out
  • Hard anodized pistons
  • ISO mounting for interchangeability
  • Anti-blowout pinion
  • Can be converted to spring return by just adding springs
  • Smooth burnished cylinder wall

Advanced Design Considerations for Best-in-Class Scotch Yoke Actuators

...
Evaluating the design features of a Best-in-Class scotch-yoke pneumatic actuator, for example the Rotex Controls DRS.

Actuator Modularity

Actuator spring modules and pneumatic modules should be able to removed, swapped, rebuilt, or reinstalled on the frame module without disassembling the frame module. No need even to remove top cover of frame module, because all bolting for removal of the modules is external.

Actuators should be easily changed in the field from fail close to fail open by just swapping the positions of the spring and pneumatic modules. No need to dismantle the frame cover or cylinder assembly.

Actuators should be able to be modified from double acting to spring return easily in the field by adding a spring module.

Springs

Springs should be lifetime lubricated and epoxy coated.

Springs should be pre-compressed inside their welded spring modules for safety and ease of use.
Pneumatic cylinders should be lined with hard chrome plating. Smooth to eliminate wear of piston seals, the surface is very hard, for long life.

Inside the pneumatic module, dual oversized tie rods should be protected from external corrosion. Where the tie rods pass through the piston head, design should include a slide bearing. This bearing is important to help maintain alignment and assure smooth operation.

Frame Module

Inside the frame module, the yoke should be supported by life time lubricated bearings. Needle roller bearings ensure the most efficient torque transmission.

The actuator should include extra heavy duty travel adjustment bolts allow for +/- 10% adjustment of the 90 degree stroke. The area of contact is large, to withstand the impact forces.

The yoke thrust pin should be made of case hardened steel to resist wear.

The piston shaft should be supported on each side of the frame module by solid bearings that ensures proper alignment and smooth operation.

Flexijoint

Each piston shaft should be equipped with two Flexijoints. These specially designed joints compensate for movement and changes in alignment to reduce internal stresses and increase output torque.

The thrust transmitted through the Flexijoints ensures no side thrust on the cylinder walls and bearings.

Unique Sealing Features

Piston seal should be an X design. Flexibility of the sealing material reduces friction, prevents leakage, and extends actuator life. The X shaped seal is wear compensating, and the unique shape of the seal retains the grease for longer periods. The piston should be guided by a PTFE thrust bearing, which helps keep the piston centered, and seal wear to a minimum.

The tie rod seal should also be X design. Old fashioned O-rings should be replaced by these flexible, low friction, resilient seals to reduce the failure rate of tie rod seals. Also reduces the wear and tear to the tie rods themselves.

Standard O-ring of the shaft seal should be replaces. In this position, a proven V-seal design should be provided. This self-energized, wear compensating seal guarantees low hysteresis and minimum friction. Like the X seal of the piston and tie rod seals, the inherent shape of the V-seal helps keep the grease where it needs to be. 

Optional Hydraulic Override

Advanced design scotch-yoke actuators should have optional hydraulic override, or the override may be retrofitted to an existing actuator.

The override is fitted into the spring cartridge, to keep the overall dimensions of the actuator and override to a minimum. It should be able to withstand up to 2,000 psi hydraulic pressure. 

Actuators 101: Quarter-turn Pneumatic Actuator Types

...
Pneumatic valve actuators come in two basic types: rack & pinion and scotch-yoke. Both style actuators provide 90 degree rotational torque to drive a quarter-turn valve (ball, plug, butterfly) open or closed.

The scotch-yoke actuator uses a piston, which moves a linear push rod that in turn engages a pivoting lever arm to provide rotation. A rack & pinion actuator uses opposing pistons with gears to engage a pinion gear shaft. The practical difference however is in size, power, torque curve and ease of adding peripherals.
rack and pinion actuator
Rack & Pinion

Rack & pinion actuators tend to be more compact, have standardized mounting patterns and have an output torque range suitable for small to medium sized valves. They include standard bolting and coupling patterns to directly attach to a valve, solenoid, limit switch or positioner.



scotch yoke actuator
Scotch-yoke

Scotch-yoke actuators, for the most part, are much larger than rack & pinion actuators and consequently provide much higher torque output. These actuators are most often used on large quarter turn valves and require careful attention to the mounting requirements because of their power.

Both styles come in either "direct acting" or "spring return" versions. Direct acting actuators use the air supply to move the actuator in both directs (open and close). Spring return actuators, as the name implies, uses springs to move the actuator back to its "resting" state.

Fire-Safe Scotch-Yoke Actuators with 3 Second Operation

...
ROTEX Scotch Yoke
Critical Service Valves with
ROTEX DRS Scotch Yoke
A Central American power generation company needed 10" and 16", Class 900, triple-offset, critical service butterfly valves to operate flawlessly and quickly in the event of fire or loss of air supply.  They chose ROTEX Controls double acting DRS Scotch-Yoke actuators with hydraulic overrides.

The actuator package also specified a (5) second or less close time, a fusable link for emergency close in the event of fire, a declutchable manual override, and ASME air receiver tanks for "fail mode" that would allow for (2) full operational cycles.

ROTEX Controls engineers also included a 3-way fusable link that supplied air to a pilot operated shuttle valve. If the system was exposed to fire, the fusible link will fail, venting the air feed to the pilot causing the shuttle valve to shift and energize the actuator.

The result was an actuator that closed the valve in under (3) seconds. Additionally, the automated packages were delivered on time and under budget!

Proper Actuator to Valve Torque Sizing

...
pneumatic actuator torque chart
A quarter turn pneumatic actuator, wether direct acting or spring return, has a given output torque based upon the air supply pressure provided. This output torque can be fairly linear, or very non-linear depending on the style of the actuator (rack and pinion vs. scotch yoke) or if the application calls for springs to be used for opening or closing.

It is critically important to properly select and match the design and torque requirements of the pneumatic actuator and the valve in any given process. Improper selection will result in failure, much higher installed cost, not to mention lost production.


There are two main ways an improperly sized actuator costs money. If the actuator is too small (underpowered at a given line pressure to provide ample seating and unseating torque), it will fail and need to be replaced. If an actuator is severely oversized, the cost of the actuation package is higher, and space is wasted accommodating the larger physical size.

Many actuator failures result before the valve and actuator are even installed because of improper sizing. Proper application engineering calls for proper use of safety factors.

A safety factor is applied when sizing a pneumatic actuator. These recommended safety factors vary slightly from manufacturer to manufacturer. However, applying a safety factor is not enough. Special consideration for the valve torque curve from fully closed to fully open must be evaluated. After the valve full-stroke torque is known, then the actuator torque curve should be evaluated side by side to assure that the safety factor exceeds all point of the valve torque curve. Otherwise, an accidental "dead-zone" where the actuator torque curve is inadequate to move the valve at a certain part of the valve stroke can happen.

Obviously, its not a good idea to apply an actuator with too small a safety factor. These actuators can add maintenance costs due to erratic operation or a higher likelihood of failing all together.

Quarter turn valves and actuators are often used in demanding application requiring high cycle rate, exposure to harsh environments and / or control critical processes such as hazardous chemicals. For these reasons a great deal of attention and care must be given to proper sizing. If you're unsure about any given application, make sure you contact an expert who can help you.

What are NAMUR Mount and Pipe Mounted Solenoid Valve Mounting Styles?

...


NAMUR
NAMUR Mount Solenoid
When selecting a solenoid valve for valve automation, the preferred mounting method needs to be considered. The two most common choices available are "NAMUR" mount and "PIPE" mount.

NAMUR
NAMUR on Actuator
NAMUR mount solenoids use a standardized "sub-plate" which months directly to the actuator on one side and to the solenoid valve on the other. This adaptor allows for quick change-out and minimizes the amount of plumbing required and is therefore less expensive to install.

Pipe
Pipe Mount Solenoid
Pipe mount solenoids use the supply piping for support and mounting. Pipe mount solenoids are less compact and require more effort to service, but can be installed on any system as you are not limited to a pre-existing pattern and have more selection in valve size.
Pipe
Pipe Mount on Actuator

Industrial Valve Limit Switches

...
ROTEX Limit Switches
In industrial valve terms, a limit switch is a device containing one or more magnetic or electrical switches, operated by the rotational or linear movement of the valve actuator. They are used to show the open or closed position of an industrial valve, or as safety interlocks to protect man or machine. The enclosure is usually classified in NEMA (National Electrical Manufacturers Association) Standards, such as NEMA 4, NEMA 4X or NEMA 7 (explosion resistant).

ROTEX Limit Switch
Internal Mechanical Limit Switch
The internal switches can be electromechanical or magnetic. Electromechanical switches respond to a mechanical cam on a shaft to change state (make or break electrical contacts). Magnetic switches use a magnetic field to change state in a reed switch, or  to sense a disruption in the magnetic field, or through capacitance.

ROTEX Limit Switch
Internal Magnetic Limit Switch
Along with an electrical signal, visual indication is an important part of a limit switch. Most switch come standard with a "dome" or "beacon" displaying "open" or "closed" or positions anywhere in between.

When applying limit switches on industrial valve application one should consider the following:


  1. Environment - is the limit switch in an area where there may be dust, spray-down, rain, corrosive gasses, combustible gases, or require sanitary conditions. Choosing the correct NEMA classification is critical.
  2. The electrical rating of the signal being transmitted. AC or DC? High voltage or low?
  3. Operation Frequency and Cycle life - will the switch only open/close occasionally, or will it cycle every few seconds? Mechanical switches have inherently shorter cycle lives than do proximity or magnetic switches. Choose the best switch considering load and cycle life.
  4. Visual indication - do you need to see the valve status from a distance? 
  5. Auxiliary outputs - besides opening of closing the primary signal, are their other signals you must send by using additional switches in the housing. 


Advanced Scotch Yoke Design Increases Service Life

...
ROTEX recently replaced some old "orange" scotch yoke actuators with the DRS series. The customer is a major international producer and marketer of food and agricultural products.  The "orange" actuators were experiencing high wear and had to be rotated out and serviced every few months. After the ROTEX DRS actors were installed, at last count, they had 125,000 cycles without any internal corrosion or degradation.

Let's examine the design improvements that allow this superior performance:
  • Pneumatic cylinders are lined with hard chrome plating. Smooth to eliminate wear of piston seals, the surface is very hard, for long life.
  • Springs are lifetime lubricated and epoxy coated.
  • Inside the pneumatic module, dual oversized tie rods are protected from external corrosion. Where the tie rods pass through the piston head, ROTEX has improved the design by providing a slide bearing, where most designs don’t. This bearing is important to help maintain alignment and assure smooth operation.
  • Inside the frame module, the yoke is supported by life time lubricated bearings. Needle roller bearings ensure the most efficient torque transmission. The piston shaft is supported on each side of the frame module by solid bearings that ensure proper alignment and smooth operation.
  • Each piston shaft of the ROTEX DRS is equipped with two Flexijoints. These specially designed joints compensate for movement and changes in alignment to reduce internal stresses and increase output torque. The thrust transmitted through the Flexijoints ensures no side thrust on the cylinder walls and bearings.
  • Piston seal is ROTEX 3X design. Flexibility of the sealing material reduces friction, prevents leakage, and extends actuator life. The 3X shaped seal is wear compensating, and the unique shape of the seal retains the grease for longer periods. The piston is guided by a PTFE thrust bearing, which helps keep the piston centered, and seal wear to a minimum.
  • The tie rod seal is also of the ROTEX 3X design. Old fashioned O-rings are replaced by these flexible, low friction, resilient seals to reduce the failure rate of tie rod seals. Also reduces the wear and tear to the tie rods themselves.
  • ROTEX has also replaced the standard O-ring of the shaft seal. In this position, we provide a proven V-seal design. This self-energized, wear compensating seal guarantees low hysteresis and minimum friction. Like the X seal of the piston and tie rod seals, the inherent shape of the V-seal helps keep the grease where it needs to be.

In 13 months, the ROTEX DRS went 125000 cycles without internal corrosion nor significant wear.

What is a Rack & Pinion Actuator?

...
According to Wikipedia, "A rack and pinion is a type of linear actuator that comprises a pair of gears which convert rotational motion into linear motion. A circular gear called "the pinion" engages teeth on a linear "gear" bar called "the rack"; rotational motion applied to the pinion causes the rack to move, thereby translating the rotational motion of the pinion into the linear motion of the rack."

Image courtesy of Wikipedia

When applied as a pneumatic valve actuator, opposing racks are attached to pistons in a cylinder. When one side is pressurized, the pinion bearing turns in one direction. When air or spring tension is applied to the opposite side, the pinion bearing turns in the other direction, thus allowing rotational motion in both directions.
ROTEX Rack and pinion actuator
Transparent actuator showing opposing pistons (ROTEX)

rack and pinion bearing
Pinion bearing and rack with piston and seal (ROTEX)
Housing which forms outer pneumatic cylinder walls (ROTEX)
Advantages of pneumatic rack and pinion actuators are compactness and space savings, reliability, durability and life cycle. Disadvantages are gear and bearing wear, piston seal fatigue and stem seal leakage.

Here is a great article on rack and pinion actuators from Valve Magazine.


What is a Scotch Yoke Pneumatic Valve Actuator?

...
According to Wikipedia, "The Scotch yoke is a mechanism for converting the linear motion of a slider into rotational motion or vice-versa. The piston or other reciprocating part is directly coupled to a sliding yoke with a slot that engages a pin on the rotating part. The shape of the motion of the piston is a pure sine wave over time given a constant rotational speed."
Animation of Scotch Yoke (courtesy of Wikipedia)

In a pneumatic actuator, the scotch yoke mechanism converts linear motion (provided by an air supply and pistons) to rotary motion. A return spring sets the rotation in the opposite direction.

Diagram of Scotch Yoke Internals (courtesy of ROTEX Controls)


Scotch yoke mechanism provides a great torque curve for many valve types and are most often used on larger valves. Additionally, as valve torque requirements increase, a scotch yoke actuator becomes a more economical choice considering production cost.

The disadvantages of scotch yoke actuators are typically the wear and tear on the pin and bearing mechanism. Manufacturers like ROTEX Controls have reduced this issue with innovative design improvements that reduce friction and wear.
ROTEX Controls DRS Scotch Yoke Actuator


Critical Service, Triple Off-Set Metal Seated Butterfly Valves with ASME Supply Tank, Fusable Links and Manual Hydraulic Over-Ride

...
16" & 10 " Triple Off-set Valves automated block valves. These are pneumatically operated valves with ASME air tanks for fail close operation on loss of electrical signal. Also included are manual hydraulic over-ride cylinders and spring loaded 3-way diverter valves with "fusible links.


After installation of valve in to pipe line, plant air is supplied to the tank inlet valve. A pipe from the tank outlet to the actuator  with filter and regulator provides the actuator clean, regulated supply air.

All electrical connections for limit switch and solenoid valves are terminated in the limit switch housing.

Valve are supplied with small 3-way ball valves with fire-safe "fusible" links and spring loaded handles that will close the valve in the event of a fire.

The manual hydraulic over-ride is used in case of loss of air, or loss of electric. 6 foot and 15 foot hydraulic lines are used to supply the hydraulic cylinders power and must be connected of the valves will not function.

As designed, these valves open in under 5 seconds and close in 1.6 seconds, have the ability to be manually over ridden in the event of a loss of air or electric, and have fire-safe spring loaded links to close the valve in the event of a fire.

Gas Over Oil Actuators for High Pressure Gas Lines

...
ROTEX Gas over oil
Gas Over Oil Actuator
Gas Over Oil actuators are used on gas transmission lines where there is sour gas (Hydrogen Sulphide) present. Because of the lack of electricity or other energy sources in remote locations, the pipeline gas is used as the energy source for the actuator, isolating the corrosive gas gas from the wetted parts of the actuator with hydraulic oil.


With the hydraulic oil energized by the pipeline gas, these actuators can operate with gas pressures up to 2000 PSI and are typically used in tandem with scotch yoke actuators (in ROTEX case the DRS, DRV, HYV or any other make of actuators). The hydraulic oil bathes the internal actuator mechanism, preventing the internal corrosion, and providing maintenance-free, high cycle and long life.

Gas-Over-Oil include a secondary storage tanks for up to 3 additional operations, in case of loss of the primary gas supply. The actuators can be used to power 1/4 turn actuators, or linear actuators for rising stem valves.

Gas over oil actuators general features include:

  • Line break control integrated with manual reset function. On exceeding the leak rate, the LBC valve operates shutdown valve and closes the main valve. Requires manual reset.
  • Torque control ensures that the actuator does not exceed the maximum seal torque for stem can be supplied. 
  • Manual hand pumps.
  • Gas filtration and dehumidification.