Advanced Design Considerations for Best-in-Class Scotch Yoke Actuators

...
Evaluating the design features of a Best-in-Class scotch-yoke pneumatic actuator, for example the Rotex Controls DRS.

Actuator Modularity

Actuator spring modules and pneumatic modules should be able to removed, swapped, rebuilt, or reinstalled on the frame module without disassembling the frame module. No need even to remove top cover of frame module, because all bolting for removal of the modules is external.

Actuators should be easily changed in the field from fail close to fail open by just swapping the positions of the spring and pneumatic modules. No need to dismantle the frame cover or cylinder assembly.

Actuators should be able to be modified from double acting to spring return easily in the field by adding a spring module.

Springs

Springs should be lifetime lubricated and epoxy coated.

Springs should be pre-compressed inside their welded spring modules for safety and ease of use.
Pneumatic cylinders should be lined with hard chrome plating. Smooth to eliminate wear of piston seals, the surface is very hard, for long life.

Inside the pneumatic module, dual oversized tie rods should be protected from external corrosion. Where the tie rods pass through the piston head, design should include a slide bearing. This bearing is important to help maintain alignment and assure smooth operation.

Frame Module

Inside the frame module, the yoke should be supported by life time lubricated bearings. Needle roller bearings ensure the most efficient torque transmission.

The actuator should include extra heavy duty travel adjustment bolts allow for +/- 10% adjustment of the 90 degree stroke. The area of contact is large, to withstand the impact forces.

The yoke thrust pin should be made of case hardened steel to resist wear.

The piston shaft should be supported on each side of the frame module by solid bearings that ensures proper alignment and smooth operation.

Flexijoint

Each piston shaft should be equipped with two Flexijoints. These specially designed joints compensate for movement and changes in alignment to reduce internal stresses and increase output torque.

The thrust transmitted through the Flexijoints ensures no side thrust on the cylinder walls and bearings.

Unique Sealing Features

Piston seal should be an X design. Flexibility of the sealing material reduces friction, prevents leakage, and extends actuator life. The X shaped seal is wear compensating, and the unique shape of the seal retains the grease for longer periods. The piston should be guided by a PTFE thrust bearing, which helps keep the piston centered, and seal wear to a minimum.

The tie rod seal should also be X design. Old fashioned O-rings should be replaced by these flexible, low friction, resilient seals to reduce the failure rate of tie rod seals. Also reduces the wear and tear to the tie rods themselves.

Standard O-ring of the shaft seal should be replaces. In this position, a proven V-seal design should be provided. This self-energized, wear compensating seal guarantees low hysteresis and minimum friction. Like the X seal of the piston and tie rod seals, the inherent shape of the V-seal helps keep the grease where it needs to be. 

Optional Hydraulic Override

Advanced design scotch-yoke actuators should have optional hydraulic override, or the override may be retrofitted to an existing actuator.

The override is fitted into the spring cartridge, to keep the overall dimensions of the actuator and override to a minimum. It should be able to withstand up to 2,000 psi hydraulic pressure. 

Fire-Safe Scotch-Yoke Actuators with 3 Second Operation

...
ROTEX Scotch Yoke
Critical Service Valves with
ROTEX DRS Scotch Yoke
A Central American power generation company needed 10" and 16", Class 900, triple-offset, critical service butterfly valves to operate flawlessly and quickly in the event of fire or loss of air supply.  They chose ROTEX Controls double acting DRS Scotch-Yoke actuators with hydraulic overrides.

The actuator package also specified a (5) second or less close time, a fusable link for emergency close in the event of fire, a declutchable manual override, and ASME air receiver tanks for "fail mode" that would allow for (2) full operational cycles.

ROTEX Controls engineers also included a 3-way fusable link that supplied air to a pilot operated shuttle valve. If the system was exposed to fire, the fusible link will fail, venting the air feed to the pilot causing the shuttle valve to shift and energize the actuator.

The result was an actuator that closed the valve in under (3) seconds. Additionally, the automated packages were delivered on time and under budget!

Proper Actuator to Valve Torque Sizing

...
pneumatic actuator torque chart
A quarter turn pneumatic actuator, wether direct acting or spring return, has a given output torque based upon the air supply pressure provided. This output torque can be fairly linear, or very non-linear depending on the style of the actuator (rack and pinion vs. scotch yoke) or if the application calls for springs to be used for opening or closing.

It is critically important to properly select and match the design and torque requirements of the pneumatic actuator and the valve in any given process. Improper selection will result in failure, much higher installed cost, not to mention lost production.


There are two main ways an improperly sized actuator costs money. If the actuator is too small (underpowered at a given line pressure to provide ample seating and unseating torque), it will fail and need to be replaced. If an actuator is severely oversized, the cost of the actuation package is higher, and space is wasted accommodating the larger physical size.

Many actuator failures result before the valve and actuator are even installed because of improper sizing. Proper application engineering calls for proper use of safety factors.

A safety factor is applied when sizing a pneumatic actuator. These recommended safety factors vary slightly from manufacturer to manufacturer. However, applying a safety factor is not enough. Special consideration for the valve torque curve from fully closed to fully open must be evaluated. After the valve full-stroke torque is known, then the actuator torque curve should be evaluated side by side to assure that the safety factor exceeds all point of the valve torque curve. Otherwise, an accidental "dead-zone" where the actuator torque curve is inadequate to move the valve at a certain part of the valve stroke can happen.

Obviously, its not a good idea to apply an actuator with too small a safety factor. These actuators can add maintenance costs due to erratic operation or a higher likelihood of failing all together.

Quarter turn valves and actuators are often used in demanding application requiring high cycle rate, exposure to harsh environments and / or control critical processes such as hazardous chemicals. For these reasons a great deal of attention and care must be given to proper sizing. If you're unsure about any given application, make sure you contact an expert who can help you.

Critical Service, Triple Off-Set Metal Seated Butterfly Valves with ASME Supply Tank, Fusable Links and Manual Hydraulic Over-Ride

...
16" & 10 " Triple Off-set Valves automated block valves. These are pneumatically operated valves with ASME air tanks for fail close operation on loss of electrical signal. Also included are manual hydraulic over-ride cylinders and spring loaded 3-way diverter valves with "fusible links.


After installation of valve in to pipe line, plant air is supplied to the tank inlet valve. A pipe from the tank outlet to the actuator  with filter and regulator provides the actuator clean, regulated supply air.

All electrical connections for limit switch and solenoid valves are terminated in the limit switch housing.

Valve are supplied with small 3-way ball valves with fire-safe "fusible" links and spring loaded handles that will close the valve in the event of a fire.

The manual hydraulic over-ride is used in case of loss of air, or loss of electric. 6 foot and 15 foot hydraulic lines are used to supply the hydraulic cylinders power and must be connected of the valves will not function.

As designed, these valves open in under 5 seconds and close in 1.6 seconds, have the ability to be manually over ridden in the event of a loss of air or electric, and have fire-safe spring loaded links to close the valve in the event of a fire.